Data Storage
The Data Storage IO-Link function can be used to save all relevant parameters of the
SLG-2 light grid in an IO-Link master. If the device is replaced, these parameters can be
written to the new device, or they can be distributed to multiple other SLG-2 light grids
with the same variant and with the same application.
NOTE
After a Data Storage download, the Teach-in status of the SLG-2 light grid is reset. This
means that a teach-in is necessary. If Auto teach-in is set, the teach-in is performed
automatically on restart.
Process data output
Transmission data
Minimum cycle time of IO-Link: 2.3 ms
Baud rate: COM3 (230.4 kbaud)
Process data length: 32 bytes
IO-Link version: 1.1.0
OPERATION 7
8026014/2021-06-10 | SICK O P E R A T I N G I N S T R U C T I O N S | SLG-2
43
Subject to change without notice