46 • Chapter 5 - Wiring Procedure ARTDriveG Instruction manual
5.6 Circuit Protection
5.6.1 External Fuses of the Power Section
The inverter must be fused on the AC Input side. Fuses, circuit breakers and slow protective switches can be used.
Superfast semiconductor fuses provide a greater degree of protection.
NOTE!
If the terminals of the DC Link circuit (C and D) are connected with external devices, semiconductor fuses
must always be fitted on the input side. This, for example, is the case with:
- connected external braking units (BU...)
- coupled DC Link circuits of several inverters
- connected external capacitors
Connections with three-phase inductance on AC input will improve the DC link capacitors life time.
Table 5.6.1.1: External Fuse Types for AC Input Side
Europe
1007
1015
1022 25000
1030 10000
2040 25000 GRD2/20 (F4D15) or Z14GR20 (F4M07) A70P20 FWP20 (S7G48)
2055 25000 GRD2/25 (F4D16) or Z14GR25 (F4M09) A70P25 FWP25 (S7G51)
2075 10000 GRD3/35 (F4D20) or Z22GR40 A70P35 FWP35 (S7G86)
3110 25000 GRD3/50 (F4D21) or Z22GR40 A70P40 FWP40 (S7G52)
3150 10000 GRD3/50 (F4D21) or Z22GR50 (F4M15) A70P40 FWP40 (S7G52)
4220 … 71320 10000
1007 50000
1015 50000
1022 50000 A70P10 FWP10 (S7G49)
1030 50000
2040 50000
2055 50000 GRD2/20 (F4D15) or Z14GR20 (F4M07) A70P20 FWP20 (S7G48)
2075 50000 GRD2/25 (F4D16) or Z14GR25 (F4M09) A70P25 FWP25 (S7G51)
3110 50000 GRD3/50 (F4D21) or Z22GR40 A70P35 FWP35 (S7G86)
3150 50000 GRD3/50 (F4D21) or Z22GR50 (F4M15) A70P40 FWP40 (S7G52)
4220 25000 GRD3/50 (F4D21) or Z22GR50 A70P50 FWP50 (S7G53)
4300 25000 S00C+üf1/80/80A/660V or Z22gR80 A70P80 FWP80 (S7G54)
4370 25000 S00C+üf1/80/100A/660V or M00üf01/100A/660V (F4G18) A70P100 FWP100 (S7G55)
5450 25000
5550 25000
6750 25000
7900 25000
71100 25000
71320 25000
2002 25000 (*)
2003 25000 (*)
2005 25000 (*) GRD2-16 (F4D14) A70P15 FWP15
(S848B)
3007 25000 (*) GRD2/25 (F4D16) or Z14GR25 (F4M09) A70P25 FWP25
(S7G51)
3010 25000 (*) Z14GR32 (F4M11) A70P30-1 FWP30A14F
(S7I50)
3015 25000 (*) GRD3/50 (F4D21) o Z22GR54 (F4M13) A70P40 FWP40
(S7G52)
3020 25000 (*)
4025 50000
4030 50000
4040 50000 Z22GR63 (F4M17) A70P60-4 FWP60B
(S7I34)
5050 50000 S00C+üf1/80/80A/660V (F4EAF) or Z22gR80 A70P80 FWP80
(S7G54)
5060 50000 S00C+üf1/80/100A/660V (F4EAG) or M00üf01/100A/660V A70P100 FWP100 (S7G55)
5075 50000 S00C+üf1/80/125A/660V F4EAJ) or M00üf01/125A/660V A70P125 FWP125 (S849B)
6100 50000 S00C+üf1/80/160A/660V (F4EAL) or M00üf01/160A/660V A70P150 (S7G56)
7125 50000 S1üf1/110/250A/660V or M1üf1/250A/660V (F4G28) A70P200 FWP200 (S7G58)
7150 50000 S1üf1/110/250A/660V or M1üf1/250A/660V (F4G28) A70P250 FWP250 (S7G59)
8200 50000 S2üf1/110/400A/660V or M2üf1/400A/660V (F4G34) A70P400 FWP400 (S7G62)
(*) 50000 [h] only with output choke
agy0700
AGy…-5 (575V)
America
AGy…-4 (230V…480V)
Connections with and/or without three-phase reactor on AC input
(S7G48)
(S7G49)
(S7G48)
(S7G49)
GRD2/10 (F4D13) or Z14GR10 (F4M03)
Connections with three-phase reactor on AC input
GRD2/10 (F4D13) or Z14GR10 (F4M03)
GRD3/50 (F4D21) or Z22GR50 (F4M15)
A70P10
A70P20
S00C+üf1/80/160A/660V or M00üf01/160A/660V (F4E15) A70P175
FWP10A14F
A70P50 FWP50 (S7G53)
(S7G49)
Drive type
F1 - Fuses type (SIEI code)
DC link capacitors life
time [h]
A70P20 FWP20
A70P10
Connections without three-phase reactor on AC input
25000
FWP175
For these types an external reactor is mandatory if the AC input impedence is equal or less than 1%
GRD2/16 (F4D14) or Z14GR16 (F4M05)
FWP10
GRD2/16 (F4D14) or Z14GR16 (F4M05)
A70P10 FWP10
GRD2/10 (F4D13) or Z14GR10 (F4M03)
FWP20
(S7G57)
(S7G62)
S1üf1/110/250A/660V or M1üf1/250A/660V (F4G28) A70P300 FWP300
S2üf1/110/400A/660V or M2üf1/400A/660V (F4G34) A70P400 FWP400
(S7G60)