PROFIBUS DP communication module
9.12 Data sets (BS)
3RW44 soft starters
202 Manual, 03/2017, NEB535219502000/RS-AB/008
Data set 94 - Reading measured values
Table 9- 25 Data set 94 - Reading measured values
504 0 Phase current I
L1
(%) 0 ... 797 % / [0 ... 255] 3.125% 8-bit current
format
L2
0 ... 797 % / [0 ... 255]
0 ... 797 % / [0 ... 255]
Remaining motor cooling time
0 ... 1 800 s / [0 ... 18 000]
0-6
0 ... 200 % / [0 ... 100]
6
7
Asymmetry ≥ 40% No asymmetry [0]
0 ... 100 Hz / [0 ... 200]
0 ... 100 Hz / [0 ... 200]
L1-L2
0 ... 1500 V / [0 ... 15000]
L2-L3
0 ... 1500 V / [0 ... 15000]
512 26 - 27 Line-to-line voltage U
L3-L1
(rms) 0 ... 1500 V / [0 ... 15000] 0.1 V
L1
0 ... 20000 A / [0 ... 2000000]
514 32 - 35 Phase current I
L2
(rms) 0 ... 20000 A / [0 ... 2000000] 0.01 A
L3
0 ... 20000 A / [0 ... 2000000]
Electronics supply voltage
0 ... 1500 V / [0 ... 15000]
-40 ... 127 °C / [-40 ... 127]
0 ... 250 °C / [0 ... 250]
519 44 - 45 Remaining cooling time of contact
0 ... 1800 s/ [0 ... 18000] 0.1 s
520 46 - 47 Remaining time for tripping of
0 ... 10000 s / [0 ... 10000] 1 s
521 48 - 51 Output power 0 ... 2147483 W /
0.1 W