Configuration instructions
3.2 Startup class
3RW44 soft starters
22 Manual, 03/2017, NEB535219502000/RS-AB/008
Application examples for normal starting (CLASS 10)
Normal starting CLASS 10 (up to 20 s with 350 % I
n
motor
)
The soft starter rating can be selected to be as high as the rating of the motor implemented.
Voltage ramp
and current
limiting
• Starting
voltage %
70 60 50 30 30 30
• Starting
time s
10 10 10 10 10 10
• Current
limiting
value
Deactivated Deactivated 4 x I
M
4 x I
M
Deactivated Deactivated
• Starting
torque
60 50 40 20 10 10
• End torque
150 150 150 150 150 150
• Starting
time
10 10 10 10 10 10
Breakaway
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Soft stop Soft stop Coasting down Coasting down Pump stop Coasting down