Diagnostics and messages
8.1 Diagnostics and messages
3RW44 soft starters
Manual, 03/2017, NEB535219502000/RS-AB/008
141
Warnings and group faults
① Warning
② Fault without restart
③ Fault with restart
No supply voltage x
1. Start command has been issued although the main voltage is not
yet applied.
Switch on the supply voltage.
2. If the message occurs in the bypass mode, it may have been
generated erroneously by a too frequently generated "Prewarning
limit - motor heating", "Remaining time for tripping" or "I
e
limit
exceeded/undershot" warning (can also be traced via the entries in
the logbook/events).
See description of applicable messages
3. Main voltage is removed simultaneously with the ON command,
although run down (not "Coasting down") is parameterized.
Activate line contactor by means of output parameterized
to ON time or parameterize "Coasting down".
Incorrect starting conditions
(for devices with product version
< *E04*)
Phase angle control faults
(for devices with product version
≥ *E04*)
x
1. Fault occurs without motor starting.
Cause:
– Motor has not been connected correctly.
– Inside-delta circuit is wrongly configured.
– There is a ground fault.
Check and correct wiring (see circuit suggestions for
inside-delta circuit).
2. Fault occurs during starting.
Cause:
– Chosen starting voltage too high
– Breakaway pulse (wrongly) set: Motor starting becomes
unstable
(set the breakaway pulse only when it is really required. In the case
of pumps, for example, a breakaway pulse often leads to misfiring.)
If there is an idle time < 5 s since the last start, the 3RW44 starts
with a higher starting voltage. In combination with a set breakaway
pulse, this can lead to "incorrect starting conditions".
Remedy: Adjust parameters or extend idle time.