PROFIBUS DP communication module
9.12 Data sets (BS)
3RW44 soft starters
212 Manual, 03/2017, NEB535219502000/RS-AB/008
ID No.
Byte
Bit
Meaning
Only in
data set
131
Value range/[coding]
Factor
43
131
Slow speed rotation factor: CW
3 ... 21 [3 ... 21]
1
198 132 Slow speed rotation factor: CCW 3 ... 21 [3 ... 21] 1
44
133
Slow speed torque CW
20 ... 100 % [4 ... 20]
5 %
199
134
Slow speed torque CCW
20 ... 100 % [4 ... 20]
5 %
135...137
Reserved = 0
Dependencies
Upper current limit > lower current limit
DC braking can only be selected when the "DC braking contactor" function is assigned to
an output.
Maximum starting time ≥ starting time
Limiting torque > starting torque
9.12.16
Data sets 132, 142, 152 - Technology parameters 3:
Reading/writing sets 1, 2, 3
Byte
Bit
Value
Note
Header
0 Coordination 0x20 Writing via C1 channel (PLC)
0x30 Writing via C2 channel (PC)
0x40 Writing 0x40 via device interface (PC)
1 - 3
Reserved = 0
Table 9- 31 Data sets 132, 142, 152 - Technology parameters 3: Reading/writing sets 1, 2, 3
ID No.
ByteBit
Meaning
Value range [coding]
Factor
4 - 9
Reserved = 0
104
10 - 11
Rated speed
500 ... 3 600 rpm [500 ... 3 600]
1 rpm
12 - 18
Reserved = 0
113
19 - 20
Rated torque
0 ... 65 535 Nm [0 ... 65 535]
1 Nm
21 - 63
Reserved = 0