PROFIBUS DP communication module
9.12 Data sets (BS)
3RW44 soft starters
204 Manual, 03/2017, NEB535219502000/RS-AB/008
Data set 96 - Reading the maximum pointer
Table 9- 27 Data set 96 - Reading the maximum pointer
656 4 Phase current I
L1 min
(%) 0 ... 797 % / [0 ... 255] 3.125% In bypass
operation
L2 min
0 ... 797 % / [0 ... 255]
Phase current I
L3 min
(%)
0 ... 797 % / [0 ... 255]
Phase current I
L1 max
(%)
0 ... 797 % / [0 ... 255]
L2 max
0 ... 797 % / [0 ... 255]
Phase current I
L3 max
(%)
0 ... 797 % / [0 ... 255]
652 12 Maximum tripping current I
A max
(%) 0 ... 1000 % / [0 ... 320] 3.125% Current during
switch-off due to
651 14 Number of motor overload trips 0 ... 65 535 / [0 ... 65 535] 1 Motor protection,
temperature
659 16 Maximum tripping current I
A max
(rms) 0 ... 20 000 A /
[0 ... 2 000 000]
0.01 A Current during
switch-off due to
660 20 Phase current I
L1 min
(rms) 0 ... 20 000 A /
0.01 A In bypass
operation
661 24 Phase current I
L2 min
(rms) 0 ... 20 000 A /
0.01 A
662 28 Phase current I
L3 min
(rms) 0 ... 20 000 A /
[0 ... 2 000 000]
0.01 A
663 32 Phase current I
L1 max
(rms) 0 ... 20 000 A /
0.01 A
664 36 Phase current I
L2 max
(rms) 0 ... 20 000 A /
0.01 A
665 40 Phase current I
L3 max
(rms) 0 ... 20 000 A /
0.01 A
Line-to-line voltage U
L1 - L2min
(rms)
0 ... 1500 V / [0 ... 15 000]
Reset to 0 in the
event of phase
failure or switch-
off of main
voltage.
L2 - L3min
0 ... 1500 V / [0 ... 15 000]
Line-to-line voltage U
L3 - L1min
(rms)
0 ... 1500 V / [0 ... 15 000]
L1 - L2max
0 ... 1500 V / [0 ... 15 000]
Line-to-line voltage U
L2 - L3max
(rms)
0 ... 1500 V / [0 ... 15 000]
L3 - L1max
0 ... 1500 V / [0 ... 15 000]
672 56 Electronics supply voltage U
NS min
(rms) 0 ... 1500 V / [0 ... 15 000] 0.1 V Reset to zero at
Electronics supply voltage U
NS max
0 ... 1500 V / [0 ... 15 000]
Maximum heatsink temperature
1 ... -40 °C/ [-40 ... 127]
Maximum contact block heating
0 ... 250 % / [0 ... 250]