PROFIBUS DP communication module
9.12 Data sets (BS)
3RW44 soft starters
208 Manual, 03/2017, NEB535219502000/RS-AB/008
Table 9- 30 Data sets 131, 141, 151 - Technology parameters 2: Reading/writing sets 1, 2, 3
ID No.
Byte
Bit
Meaning
Only in
data set
131
Value range/[coding]
Factor
120
4 ... 7
Device functions_2
X
1 8 ... 11 Device functions_1 X
130
12
Rated operational current I
e
0 ... 2 000 A [0 ... 200 000]
0.01 A
3
16
0
Load type
X
3-phase [0]
4 16
1
Protection against voltage failure X
No [0]
Yes [1]
16
2...7
Reserved = 0
136
17
Prewarning limit - motor heating
X
0 ... 95 % [0 ... 19]
5 %
5 18
0...2
Response to overload - thermal
motor model
X
Tripping without restart [0]
Tripping with restart [1]
Warning [2]
18
3...7
Reserved = 0
6 19
0...4
Tripping class X
CLASS 5 (10a) [3]
CLASS 10 [0]
CLASS 15 [4]
CLASS 20 [1]
CLASS 30 [2]
CLASS OFF [15]
19
5...7
Reserved = 0
7
20
Recovery time
X
60 ... 1 800 s [2 ... 60]
30 s
8
21
Idle time
X
0 ... 255 s [0 ... 255]
1 s
137 22...23 Prewarning limit - remaining time
for tripping
X 0 ... 500 s [0 ... 500] 1 s
10 24
0...1
Response to overload -
temperature sensor
X
Tripping without restart [0]
Tripping with restart [1]
Warning [2]
24
2...3
Reserved = 0
9 24
4...6
Temperature sensor X
Deactivated [0]
Thermoclick [1]
PTC type A [2]
12 24
7
Temperature sensor monitoring X
No [0]
Yes [1]
25...26
Reserved = 0
15
28
Lower current limit
18.75 ... 100 % [6 ... 32]
3.125%
16
29
Upper current limit
50 ... 150 % [16 ... 48]
3.125%
30...31
Reserved = 0
32
0...5
Reserved = 0