PROFIBUS DP communication module
9.12 Data sets (BS)
3RW44 soft starters
208 Manual, 03/2017, NEB535219502000/RS-AB/008
Table 9- 30 Data sets 131, 141, 151 - Technology parameters 2: Reading/writing sets 1, 2, 3
1 8 ... 11 Device functions_1 X
Rated operational current I
e
0 ... 2 000 A [0 ... 200 000]
0
4 16
1
Protection against voltage failure X
• No [0]
• Yes [1]
16
2...7
Reserved = 0
Prewarning limit - motor heating
5 18
0...2
Response to overload - thermal
motor model
X
• Tripping without restart [0]
• Tripping with restart [1]
• Warning [2]
3...7
6 19
0...4
Tripping class X
• CLASS 5 (10a) [3]
• CLASS 10 [0]
• CLASS 15 [4]
• CLASS 20 [1]
• CLASS 30 [2]
• CLASS OFF [15]
5...7
60 ... 1 800 s [2 ... 60]
137 22...23 Prewarning limit - remaining time
X 0 ... 500 s [0 ... 500] 1 s
10 24
0...1
Response to overload -
temperature sensor
X
• Tripping without restart [0]
• Tripping with restart [1]
• Warning [2]
2...3
9 24
4...6
Temperature sensor X
• Deactivated [0]
• Thermoclick [1]
• PTC type A [2]
12 24
7
Temperature sensor monitoring X
• No [0]
• Yes [1]
18.75 ... 100 % [6 ... 32]
0...5