PROFIBUS DP communication module
9.12 Data sets (BS)
3RW44 soft starters
210 Manual, 03/2017, NEB535219502000/RS-AB/008
35 52...53 Substitute value X The "Substitute value" parameter is only
relevant if the "Response to CPU/master
STOP" parameter has been set to "Switch
substitute value", see Process data and
process images (Page 170)
• Motor CW 52 [0]
• Motor CCW (only if 52 [6] active) 52 [1]
• Trip reset 52 [3]
• Emergency start 52 [4]
• Slow speed 52 [6]
• Output 1 53 [0]
• Output 2 53 [1]
• Parameter set bit 0 53 [2]
• Parameter set bit 1 53 [3]
0...5
36 56
6
Group diagnostics X
• Disable [0]
• Enable [1]
34 56
7
Response to CPU/master STOP X
• Switch substitute value [0]
• Hold last value [1]
26 76 Input 1 - action X
• No action (default) [0]
• Manual mode local [6]
• Emergency start [7]
• Slow speed [10]
• Quick stop [11]
• Trip reset [12]
• Motor CW with PS1 [16]
• Motor CCW with PS1 [17]
• Motor CW with PS2 [18]
• Motor CCW with PS2 [19]
• Motor CW with PS3 [20]
• Motor CCW with PS3 [21]
Input 2 - (see Input 1 - action)
Input 3 - (see Input 1 - action)
Input 4 - (see Input 1 - action)