Commissioning
6.4 Making settings in the selected parameter set
3RW44 soft starters
74 Manual, 03/2017, NEB535219502000/RS-AB/008
"Motor heating" startup mode
Motor thermal capacity
CAUTION
May lead to damage to property.
The "Motor heating" startup mode is not a continuous operating mode. The motor must be
equipped with a temperature sensor (Thermoclick/PTC) to ensure motor protection. The
motor model with integrated electronic motor overload protection is not suitable for this kind
of operation.