APPENDIX 3 EQUIPMENT GROUPING TABLE
Equipment type
Detecting
group
Control
output
group
Supervision
group
Fire display
panel group
FDO181 Smoke detector
√ √
FDT181 Heat detector
√ √
FDM181 Manual Call Point
√ √
FDHM181 Hydrant Manual Call Point
√ √
FDCI181 Input module
√
FDCIO181 Input/output module
√
Main board supervision input
√ √
Main board confirmation input
√ √
Main board alarm input
√ √
Main board output, interlocking panel output (without
confirmation)
√ √
Main board output, interlocking panel output (with
confirmation)
√ √
NAC
√
Main power
√
Battery
√
Charging circuit
√
Printer
FDCL181 Isolator
√
FDCI181 Input module/ FDCIO181 Input/output module
supervision input
√ √
FDCI181 Input module/ FDCIO181 Input/output module
confirmation input
√ √
FDCI181 Input module/ FDCIO181 Input/output module alarm
input
√ √
FDCI181 Input module/ FDCIO181 Input/output module output
(without confirmation)
√ √
FDCI181 Input module/ FDCIO181 Input/output module output
(with confirmation)
√ √
Note:
- One device can be assigned to max. 10 groups AND 6 FRT groups.
- Relations among equipments of control output group is “and” relations. Relations among equipments of
supervision and detection group is “or” relations.
- Alarm and trouble information of equipments of fire display panel group can be displayed on the display
panel.
- Equipments must be put into groups to participate interlocking relation program.