APPENDIX 1 PARAMETER LIST
Equipment type Editable item Parameter description
System Text System name
Station
- FC1820
- FC1840
Text Controller name
Login time Under 2nd/3rd level, if there is no operation in preset login time, controller
will automatically log out to 1
st
level. Effective value: 1-60 minutes.
Walk-test time When controller is being tested, it will automatically resume to normal status
after preset walk-test time, without the need of manual operation. Effective
value: 1-60 minutes.
Sound level Setup sound volume of beeper, with effective value of 0-7. When the value
is 0, it is silence mode.
LCD closing time If there is no operation of controller in preset LCD off time, LCD will shut off
back light. Effective value: 1-60 minutes.
Main board input/output Text Main board input/output (default)
P2 line Text P 2 circuit #
Topology type Option 1: Stub
Option 2: Loop (default)
Power supply Text Power supply (default)
Interlocking panel Text Interlocking panel (default)
FDO181 Smoke detector Text Equipment location description
Sensitivity Option 1: Standard (default)
Option 2: Sensitive
FDT181 Heat detector Text Equipment location description
Detector mode Option 1: A2S (constant temperature) (default)
Option 2: A2R (Difference/constant temperature)
FDM181 Manual call point Text Equipment location description
FDHM181 Hydrant manual
call point
Text Equipment location description
FDCI181 Input module Text Equipment location/function description
FDCIO181 Input/output
module
Text Equipment location/function description
Supervision input
(FDCI181&FDCIO181)
Text Equipment location/function description
Inversion Option 1: Normal (Active When NO is closed) (default)
Option 2: Inverting (Active when NC is open)
Supervision input
(interlocking panel and
main board input)
Text Equipment location/function description
Status input
(FDCI181&FDCIO181)
Text Equipment location/function description
Status input
(interlocking panel and main
board input)
Text Equipment location/function description
Fire alarm input
(FDCI181&FDCIO181)
Text Equipment location/function description