RT interface FCI2005-N1 [NL]
104
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
20.4 Adjustment elements
The switching contacts of the relays K1 … K12 must be configured as 'normally
open' (NO) or 'normally closed' (NC). The application-specific settings are made by
inserting a wire jumper or a resistor between the corresponding solder pins.
The following figure shows the setting of the relay K5 as an example.
NC
NO
X43
X44
X20
X19
K5
REL5_OUT-
REL5_OUT+
Example: Setting the switching contacts
Settings
NO = wire jumper or resistor between solder pins X19 and X43
NC = wire jumper or resistor between solder pins X20 and X44
Settings for Holland (default)
Relay Contact Solder pins NO/NC Resistance
X19 … X43 NO 680 Ω K5 REL5_OUT+
X20 … X44 NC 3.3 kΩ
X21 … X45 NO 680 Ω K6 REL6_OUT+
X22 … X46 NC 3.3 kΩ
X23 … X47 NO 680 Ω K7 REL7_OUT+
X24 … X48 NC 3.3 kΩ
X25 … X49 NO 680 Ω K8 REL8_OUT+
X26 … X50 NC 3.3 kΩ