Periphery board (1-loop) FCI2001-A1
38
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
Element Des. Function
H113 (H100, H101, H114, H115 not used)
H114 Not used
H115 Not used
F400 Horn output (1 A/T); Schurter OMT 125
F401 Supply output 1 (1 A/T); Schurter OMT 125
F402 Not used
F501 Monitored alarm output (1 A/T); Schurter OMT 125
Fuses
F601 Monitored fault output (1 A/T); Schurter OMT 125
Adjustment elements S100 Switchover of the LED indicators for the inputs and outputs
8.2 Pin assignments
Inputs and outputs which are not used do not require termination.
C-NET detector lines which are not used must not be terminated.
8.2.1 X1 supply
PIN Designation Description
1 #BATT Message input from the power supply: Battery fault
2 #CONV Message input from the power supply: Converter fault
3 #MAINS Message input from the power supply: Mains failure
4 COMMON Ground
5 3SRC+ Supply input for third supply source (+) [FR]
6 3SRC– Supply input for third supply source (-) [FR]
7 VSYS+ Supply input from the power supply (+)
8 VSYS+ Supply input from the power supply (+)
9 VSYS– Supply input from the power supply (–)
10 VSYS– Supply input from the power supply (–)
Admissible cable cross-section: 0.2 ... 2.5 mm²