Floor repeater display FT2011
117
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
24.2 Pin assignments
24.2.1 X101 detector line and external supply
PIN Designation Description
1 LINE+ Detector line (+)
2 LINE– Detector line (-)
3 LINE+ Detector line (+)
4 LINE– Detector line (-)
5 AC+ External supply DC+/AC
6 AC- External supply DC-/AC
7 Not connected
8 Not connected
4
3
6
5
X101
8
7
AC+
2
1LINE+
LINE-
LINE+
LINE-
AC-
-
+
+
-
DC+/AC
DC-/AC
+
-
+
-
+
-
24.3 Adjustment elements
DIP switch
S14
Des. Function Position Meaning
ON Acoustic signaling deactivated 1 3TE_OFF Acoustic signaling in case of failure of
the C-NET supply and external supply
OFF Acoustic signaling activated (ex-
works default setting)
2 WD_OFF No function; switch must always be in
position 'OFF'.
OFF Ex-works default setting