Periphery board (1-loop) FCI2001-A1
42
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
8.3 Indications
Indications of supply and system
LED Colour Function Condition Meaning
Off Normal operation H1 Red Power Down Ready
On Control panel may be disconnected from the
mains.
Off Fuse ok H401 Yellow Supply output 1 (F401)
On Fuse damaged
Off Fuse ok H501 Yellow Monitored alarm output (F501)
On Fuse damaged
Off Fuse ok H601 Yellow Monitored fault output (F601)
On Fuse damaged
Indication of outputs
LED Colour Function Condition Meaning
Off Relay activated (default) H102 Yellow FUE_FAU_1
On Relay not activated
Off Active (default)
Slow Open line
Fast Short-circuit
H103 Yellow FUE_FAU_2
On Passive
Off Relay not activated (default) H104 Yellow FUE_AL_1
On Relay activated
Off Passive (default)
Slow Open line
Fast Short-circuit
H105 Yellow FUE_AL_2
On Active
Off Passive (default)
Slow Open line
Fast Short-circuit
H106 Yellow HORN_1
On Active