Fire department periphery module FCI2001-D1 [DE]
67
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
12.2 Pin assignments
Inputs and outputs which are not used do not require termination.
12.2.1 X2 fire department operating panel / X3 fire department operating
panel
X2 fire department operating panel
PIN Designation Description
8 +24V Operating voltage (+24 V)
7 0V Operating voltage (-)
6 UE ausgel Transmission transmission triggered
5 LA ausgel Extinguishing system triggered
4 Bf St ab Fire controls off
3 Ak Sign ab Acoustic signals off
2 BMZ rueckst Reset fire control panel
1 UE ab Remote transmission off
Admissible cable cross-section: 0.2 ... 1.5 mm²
X3 fire department operating panel
PIN Designation Description
8 Bf St ab Fire controls off
7 Ak Sign ab Acoustic signals off
6 BMZ rueckst Reset fire control panel
5 UE ab Remote transmission off
4 UE pruefen Check remote transmission
3 Reserve Reserve output
2 Reserve Reserve input
1 Not used
Admissible cable cross-section: 0.2 ... 1.5 mm²