Repeater (SAFEDLINK) FN2002-A1
81
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
Notes
In the C-WEB, line 1 must always be wired to line 2, and line 2 must be wired to
line 1.
16.3 Indications
LED Colour Function Condition Meaning
Flashes Normal condition H1 Green Condition of the repeater
(SAFEDLINK)
Off Repeater (SAFEDLINK) is defective
On Error on connection line 2;
repeater (SAFEDLINK) is OK
H2 Yellow Condition of the line 2
(A2, B2)
Off Normal condition
On Error on connection line 1;
repeater (SAFEDLINK) is OK
H3 Yellow Condition of the line 1
(A1, B1)
Off Normal condition
On Earth fault on connection line 2;
repeater (SAFEDLINK) is OK
H4 Red Ground fault
Off Normal condition