LED indicator (internal) FTO2002-A1
83
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
17.2 Adjustment elements
The LED indicator (internal) is assigned an address by means of the switches.
Switch S15 Meaning
1 2 3 4 5 6
Test mode (lamp test)
ON Device address 1
ON Device address 2
ON ON Device address 3
ON Device address 4
ON ON Device address 5
ON ON Device address 6
ON ON ON Device address 7
ON Device address 8
ON ON Device address 9
ON ON Device address 10
ON ON ON Device address 11
ON ON Device address 12
ON ON ON Device address 13
ON ON ON Device address 14
ON ON ON ON Device address 15
ON Device address 16
Blank fields = Switch in 'OFF' position
Each address can be assigned only once per station.