Power supply (70W) FP2001-A1
19
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
WARNING
High voltage! Danger to life!
Electric shock
z Connect the power supply to the mains only when the cover is closed.
4.2 Pin assignments
4.2.1 X1 mains connection
PIN Designation Description
1
Ground (protective conductor PE)
2 N Neutral conductor
3 L External conductor (L1)
Admissible cable cross-section: 0.2 ... 2.5 mm²
4.2.2 X2 monitoring signals
PIN Designation Description
8 Battery Detection line (#BATT): Battery fault
7 Convert Detection line (#CONV): Power supply fault
6 Main Detection line (#MAINS): Mains fault
5 Common GND Ground (COMMON)
4 Usys + System supply (VSYS+)
3 Usys – System supply (VSYS-)
2 Akku + Battery supply (+)
1 Akku – Battery supply (-)
Admissible cable cross-section: 0.2 ... 2.5 mm²
7
8
5
6
X2
3
4
Main
Common GND
Akku +
VSYS-
VSYS+
Convert
Battery
2
1
-
+
Usys +
-
+
Usys -
Akku -
#BATT
#CONV
#MAINS
COMMON
1
F103
F102
1 Cable tree to periphery board or fire
terminal board