Mimic display driver FT2001-A1
124
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
25.3 Indications
LED Colour Function Condition Meaning
Lit up Normal condition
Fast flashing
(0.5 s)
Communication error C-NET or degraded mode of the control
panel
LED_1
(X8)
(Green) Operating LED
Slow flashing
(1 s)
Voltage error of the external supply or not yet configured
Off Normal status (update mode inactive) H201 Yellow Update mode
Flashes Update mode active
25.4 Adjustment elements
DIP switch S200 activates update mode manually via the MC-Link connection.
Firmware update mode is generally started automatically and the switch S200 does
not have to be changed over. If update mode is not started automatically, it is
possible to switch over manually with S200.
Switch Function Position Meaning
ON Update mode active S200-1 Firmware update mode
OFF Update mode inactive
S200-2 Not connected