Fire terminal board FTI2001-A1
35
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
X7, supply input 1
PIN Designation Description
4 VSYS - 1 Ground
3 VSYS - 1 Ground
2 VSYS + 1 System supply 21 … 28.6 V DC (+)
1 VSYS + 1 System supply 21 … 28.6 V DC (+)
Admissible cable cross-section: 0,2 ... 2,5 mm²
4
3
X7
VSYS -1
VSYS -1
2
1
VSYS +1
VSYS +1
-
+
-
+
7.3 Indications
LED Color Function Conditio
n
Meaning
Off Normal operation H101 …
H103
Red Power Down Ready
On Control panel may be disconnected from the
mains
Off Fuse ok H201 Yellow Supply output 1
On Fuse damaged
Off Fuse ok H202 Yellow Supply output 2
On Fuse damaged
Off Supply available H203 Yellow Surveillance of the voltage at the supply
input 2 'VSYS2' *
On No supply and surveillance is switched on
(S1-1 = ON)
Off Supply available H204 Yellow Surveillance of the voltage at the supply
input 1 'VSYS1' *
On No supply and surveillance is switched on
(S1-2 = ON)
On Fault in the power supply unit H207 Yellow Power supply surveillance
'CONVERT_DEF_IN'
Off Normal condition
On No mains voltage H206 Yellow Mains voltage surveillance
'MAINS_FAIL_IN'
Off Normal condition
On Battery fault H205 Green Battery surveillance
'BATT_DEF_IN'
Off Normal condition
* For a correct indication the switch S1 must be in the corresponding position!