Periphery board (2 loops) FCI2002-A1
45
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
Element Des. Function
H1 Power Down Ready
H201 C-NET module 2 indication
H401 Monitoring supply output 1 (fuse F401)
H402 Monitoring supply output 2 (fuse F402)
H501 Monitoring alarm output (fuse F501)
H601 Monitoring fault output (fuse F601)
LEDs
H100-
H115
Indications of programmable inputs and outputs
F400 Horn output (1 A/T); Schurter OMT 125
F401 Supply output 1 (1 A/T); Schurter OMT 125
F402 Supply output 2 (1 A/T); Schurter OMT 125
F501 Monitored alarm output (1 A/T); Schurter OMT 125
Fuses
F601 Monitored fault output (1 A/T); Schurter OMT 125
Adjustment elements S100 Switchover of the LED indicators for the inputs and outputs
9.2 Pin assignments
Inputs and outputs which are not used do not require termination.
C-NET detector lines which are not used must not be terminated.
9.2.1 X1 supply
PIN Designation Description
1 #BATT Message input from the power supply: Battery fault
2 #CONV Message input from the power supply: Converter fault
3 #MAINS Message input from the power supply: Mains failure
4 COMMON Ground
5 3SRC+ Supply input for third supply source (+) [FR]
6 3SRC– Supply input for third supply source (-) [FR]
7 VSYS+ Supply input from the power supply (+)
8 VSYS+ Supply input from the power supply (+)
9 VSYS– Supply input from the power supply (–)
10 VSYS– Supply input from the power supply (–)
Admissible cable cross-section: 0.2 ... 2.5 mm²