Operator unit FCMxxxx
29
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
6.2 Indications
LED Color Function Condition Meaning
Off No Ethernet connection H32 Yellow LINK control indicator
On Ethernet connection established
Off Processor in normal operation H36 Yellow Processor status indicator
On Processor in degraded mode; replace
component or contact hotline
Off Processor in normal operation H37 Red Processor status indicator
On Processor in degraded mode
Off Installation in operation H38 Red Installation ready for switching off
On Installation may be disconnected from the
mains
Off Processor in normal operation H39 Red Processor status indicator
On Processor in degraded mode; replace
component or contact hotline
H297 Red Reserved
6.3 Adjustment elements
S32: Reset key
Operation Function
Press briefly
The station is shut down in a controlled manner.
After the station has shut down, the 'Power down ready' LED lights up.
This may take up to 5 minutes!
The station may now be disconnected from the supply.
Press for
approx. 5 s
Hardware reset
The station is shut down immediately and rebooted. This may lead to data
loss.
S33: Switch for the ground fault monitoring of the Ethernet
connection
S33-1 S33-2 Function
ON ON Ground fault monitoring switched on
OFF OFF Ground fault monitoring switched off
OFF ON Not admissible
ON OFF Not admissible
Note:
The two switches must always be in the same position!