Periphery board (1-loop) FCI2001-A1
37
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
8 Periphery board (1-loop) FCI2001-A1
8.1 Views
1
1
H402
H401
H1
H501
S100
H102
H115
H100
H101
H114
H113
1111
1
F402
F401
F601
F501
F400
X8
X7
X6
X11
X40
X400
X3
X1
1
X14
H601
H201
X15
1
PCB view of periphery board (1-loop) FCI2010
Element Des. Function
X1 Supply connection
X3 Connection periphery bus to the PMI & mainboard
X6 Monitored outputs for alarm, fault and horn
X7 Changeover contacts for RT Alarm and RT Fault
X8 Configurable inputs/outputs 1 … 4, supply input 1
X11 C-NET detector line, loop 1 (mod. 2)
Plugs and terminals
X400 Connection periphery bus for additional peripherals
X15 Not used
X40 Not used
Slots for modules
X14 Not used
H1 Power Down Ready
H201 C-NET module 2 indication
H401 Monitoring supply output 1 (fuse F401)
H402 Not used
H501 Monitoring alarm output (fuse F501)
H601 Monitoring fault output (fuse F601)
LEDs
H102- Indications of programmable inputs and outputs