Repeater (SAFEDLINK) FN2002-A1
79
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
16 Repeater (SAFEDLINK) FN2002-A1
16.1 Views
1
X4
H1
H2
H3
H4
X
2
1
8
41
111
X5 X6 X7
PCB view of repeater FN2002
X1 Not used for operation.
Connector with full population for programming with firmware
X2 Connector for external power supply and the transmission to additional repeaters
X3 Connector for C-NET and earth connection
X4 Jumper for the switching over of the data rate (switchover during operation has no
effect)
X5 Jumper for earthing X3/pin 3
X6 Jumper for earthing X3/pin 5
X7 Jumper for earthing X3/pin 6
H1 LED green, status indicator of the repeater
H2 LED yellow, status indicator for line 2
H3 LED yellow, status indicator for line 1
H4 LED red, earth fault indication for line 2