EVAC-NL operating unit FTO2007-N1 [NL]
88
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
18.4 Adjustment elements
The EVAC-NL indicator is configured with the switch S20.
Setting for one or first EVAC-NL
Switch S20 Meaning
1 2 3 4 5 6
S0 S1 S2 Master Syn (Empt
y)
ON OFF Device address 1 *
ON ON OFF Device address 2
ON ON OFF Device address 3
ON ON ON OFF Device address 4
ON ON OFF Device address 5
X X X ON ON Mimic display outputs are actuated and
polled (LED, keys and key switch)
Blank fields = Switch in 'OFF' position
X = Switch position has no impact
* If working with one single EVAC-NL indicator (10 zones) and if working with the
first EVAC-NL indicator, S20/4 (Master) must always be set to ON. If used in the
EVAC-NL mimic display driver, the S20/5 (Syn) switch must also be ON.
Each address can be assigned only once per station.
The factory setting is always made for the application in question.
Setting for the second and/or any subsequent EVAC-NL indicator
Switch S20 Meaning
1 2 3 4 5 6
S0 S1 S2 Master Syn (Empt
y)
OFF OFF Device address 1
ON OFF OFF Device address 2 *
ON OFF OFF Device address 3
ON ON OFF OFF Device address 4
ON OFF OFF Device address 5
X X X OFF ON Mimic display outputs are actuated and
polled (LED, keys and key switch)
Blank fields = Switch in 'OFF' position
X = Switch position has no impact
* = 2 EVAC-NL indicators must not be operated on the same address (per station).
On the second or any subsequent indicator, the address must always be set 1
higher (slave). If used in the EVAC-NL mimic display driver, the S20/5 (Syn) switch
must also be ON.
Each address can be assigned only once per station.
The factory setting is always made for the application in question.