Periphery board (4 loops) FCI2004-A1
54
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
Element Des. Function
X401 Connection periphery bus for additional peripherals
X14 Not used
X15 Loop extension (C-NET) FCI2003 for the integrated line card 1
X24 Not used
X25 Loop extension (C-NET) FCI2003 for the integrated line card 2
Slots for modules
X40 Not used
H1 Power Down Ready
H250 C-NET module 2 indication
H850 C-NET module 3 indication
H401 Monitoring supply output 1 (fuse F401)
H402 Monitoring supply output 2 (fuse F402)
H501 Monitoring alarm output (fuse F501)
H601 Monitoring fault output alarm output (fuse F601)
LEDs
H100-
H120
Indications of the programmable I/Os
F400 Horn output 1 (1 A/T); Schurter OMT 125
F401 Supply output 1 (1 A/T); Schurter OMT 125
F402 Supply output 2 (1 A/T); Schurter OMT 125
F403 Horn output 2 (1 A/T); Schurter OMT 125
F501 Monitored alarm output (1 A/T); Schurter OMT 125
Fuses
F601 Monitored fault output (1 A/T); Schurter OMT 125
Adjustment elements S100 Switchover of the LED indicators for the I/Os