Periphery board (4 loops) FCI2004-A1
56
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
10.2.2 X5 monitored horn outputs 1 and 2
PIN Designation Description
4 SOUND2- Horn output 2 (-)
3 SOUND2+ Horn output 2 (+)
2 SOUND1- Horn output 1 (-)
1 SOUND1+ Horn output 1 (+)
Admissible cable cross-section: 0.2 ... 1.5 mm²
+
-
1
2
X5
SOUND2-
SOUND2+
F403 +
-
3
4
SOUND1-
SOUND1+
2.3 ... 5.5 k
2.3 ... 5.5 k
F400
10.2.3 X6 alarm and fault monitored outputs
PIN Designation Description
4 FAU_OUT Output fault
3 VSYS_O Supply output for consumer fault
2 AL_OUT- Alarm output (-)
1 AL_OUT+ Alarm output (+)
Admissible cable cross-section: 0.2 ... 1.5 mm²
3
4
1
2
X6
+
-
AL_OUT-
AL_OUT+
FAU_OUT
VSYS_0
F601
+
-
F501
2.3 ... 5,5 k
1.6 ... 2.3 k
1
1
1 Remote transmission