Operating the contactor panel with panel width 435 mm
110-0134.9 / 14 NXAIR / 40 kA 113
Fit a padlock (optional) to the door handle and close it.
The high-voltage door is closed.
13.6 Positions of the contactor truck
General description of positions of the contactor truck:
Service position
The contactor truck is connected with the busbar system and the outgoing feeder. The auxiliary circuit of the
contactor truck is connected through the low-voltage connector.
Test position
The contactor truck is disconnected from the busbar system and the outgoing feeder. The auxiliary circuit of
the contactor truck is connected through the low-voltage connector.
Disconnected position
The contactor truck is disconnected from the busbar system and the outgoing feeder. The auxiliary circuit is
disconnected by pulling out the low-voltage connector.
Short instruction for racking the contactor truck:
Racking the contactor truck manually from test / disconnected position to service position:
Step 1
Insert and turn double-bit key
Step 2
Insert and turn
racking crank
as far as it will go
and pull it off
Step 3
Turn and remove double-bit key
from
by
to
from
by
to
Racking the contactor truck manually from service position to test / disconnected position:
Step 1
Insert and turn double-bit key
Step 2
Insert and turn
racking crank
as far as it will go
and pull it off
Step 3
Turn and remove double-bit key
from
by
to
from
by
to
90°
90°
90°
90°