110-0134.9 / 13 NXAIR / ≤ 40 kA 98
Operating the disconnecting panel
11 Operating the disconnecting panel
Read and understand these instructions before attempting operating works.
11.1 Control elements at the front side of the panel
Door to the low-voltage compartment
Locking device for the door to the low-voltage compartment
Instruction label for closing the high-voltage door
Actuating opening for racking the withdrawable
disconnector link / disconnector truck
Handle for opening the high-voltage door
Actuating opening for inserting the double-bit key to control
racking of the withdrawable disconnector link /
disconnector truck
Mechanical position indicator for withdrawable disconnector
link / disconnector truck
Actuating opening for operating the feeder earthing switch
Operating slide for opening and closing the actuating
opening for operating the feeder earthing switch
Mechanical position indicator for feeder earthing switch
Operating slide for opening and closing the actuating
opening for racking the withdrawable disconnector
link / disconnector truck
Test sockets for busbar voltage detecting system
(type LRM) as additional component
Fig. 164: Control elements on the panel front
11.2 Position indicators visible on high-voltage door
Withdrawable disconnector link /
disconnector truck:
Service position, intermediate position or
test position
Feeder earthing switch:
CLOSED position or OPEN position