EasyManuals Logo

Siemens NXAIR User Manual

Siemens NXAIR
436 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #199 background imageLoading...
Page #199 background image
Operating the contactor panel with panel width 600 mm
110-0134.9 / 14 NXAIR / ≤ 40 kA 199
Requirements
The coordination of the components of the motor circuit requires the following:
• The let-through current I
D
must not exceed 46 kA at 7.2 kV.
• In case of low-voltage supply via a control transformer, short-circuit currents ranging above the limit
breaking capacity must be interrupted within 80 ms. This requirement does not apply if
• the mechanical latch is provided
or
• the opening times have been extended so much that – in the a.m. current range – the contactor
can only open when the fuse-link has interrupted the current.
• Due to the arising motor starting current, the instant when the motor starts represents the maximum
stress for the HV HRC fuse-link. This stress must neither operate nor pre-damage the fuse-link.
• Other factors of influence on the stress of the HV HRC fuse-links are the starting time and the
starting frequency of the motors.
14.22 Replacing protection fuse-links for the control transformer
Arrangement of protection fuse-links
The control transformer (2) is equipped with 2 protection fuse-links (1). The protection fuse-links are only
accessible after removing the HV HRC fuse-links from the outer phases.
Fig. 356: Rear side of truck: Arrangement of
protection fuse-links for control transformer
1
2

Table of Contents

Other manuals for Siemens NXAIR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens NXAIR and is the answer not in the manual?

Siemens NXAIR Specifications

General IconGeneral
BrandSiemens
ModelNXAIR
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals