39 NXAIR / ≤ 40 kA 110-0134.9 / 13
Operating the circuit-breaker panel
10 Operating the circuit-breaker panel
Read and understand these instructions before attempting operating works.
10.1 Control elements at the front side of the panel
Fig. 48: Control elements on the panel
front of the circuit-breaker panel
Door to the low-voltage compartment
Locking device for the door to the low-voltage
compartment
Test sockets for busbar voltage detecting system
(type LRM) as additional component
Instruction label for closing the high-voltage door
Opening for charging the spring energy store in the
circuit-breaker manually (covered)
Spring state indicator for the closing spring
Handle for opening the high-voltage door
Operating slide for opening and closing the actuating
opening for racking the withdrawable
circuit-breaker / circuit-breaker truck
Actuating opening for racking the withdrawable
circuit-breaker / circuit-breaker truck
Actuating opening for inserting the double-bit key to
control racking of the withdrawable
circuit-breaker / circuit-breaker truck
Mechanical position indicator for withdrawable
circuit-breaker / circuit-breaker truck
Actuating opening for operating the feeder
earthing switch
Operating slide for opening and closing the actuating
opening for operating the feeder earthing switch
Mechanical position indicator for feeder
earthing switch
CLOSED/OPEN indicator of the circuit-breaker
Operations counter for circuit-breaker
Actuating opening for opening the circuit-breaker
Actuating opening for closing the circuit-breaker
Rotary button to close and open the actuating opening
located below