Panels with motor operating mechanism control
110-0134.9 / 14 NXAIR / ≤ 40 kA 405
Conflicting operation
The requirement of setting the panel to either local or remote control prevents
operating the panel locally and centrally at the same time.
For any local operations ─ manual or electrical ─ set the panel to local
control, for example by switching the local-remote switch to LOCAL
position.
Covered control elements
For safety reasons, the actuating opening for closing the circuit-breaker is covered
by the control door.
Open the control door to uncover the actuating opening on the high-
voltage door.
The procedure for closing the circuit-breaker manually in panels with motor operating mechanism control is
identical with the procedure in panels without motor operating mechanism control.
For closing the circuit-breaker manually, see chapter 10.12.
27.13 Charging / discharging the spring energy store manually
Charging the spring energy store manually is carried out by inserting a hand crank through an actuating
opening in the high-voltage door, and turning it subsequently. Discharging can only be done manually. It is
carried out by pushing a rod alternately through the actuating openings for opening / closing the circuit-
breaker.
Charging and discharging manually can only be carried out when the control door is open. However, the
indicators for the circuit-breaker position and the closing spring state can still be seen through an inspection
window after closing the control door.
Fig. 731: Circuit-breaker type 3AE1:
Actuating openings for
charging / discharging
the spring energy store
Fig. 732: Circuit-breaker type 3AE5:
Actuating openings for
charging / discharging
the spring energy store
Opening for charging
the spring energy store
in the circuit-breaker
manually (covered)
Actuating opening for
closing the
circuit-breaker
Actuating opening for
opening the
circuit-breaker