Verifying safe isolation from supply
110-0134.9 / 14 NXAIR / ≤ 40 kA 269
Phase not isolated from supply
Phase not isolated from supply
Indication does not light up or
does not flash
Phase isolated from supply
Indication does not light up or does not flash.
Refit the cover on the test socket.
Proceed in the same way with the test sockets for L2, and then for L3.
Safe isolation from supply is verified as soon as L1, L2 and L3 have been determined to be
isolated from supply.
20.6 CAPDIS and VOIS systems overview
Integrated capacitive voltage detecting system
Integrated capacitive voltage monitoring system with relay output
Economic integrated capacitive voltage detecting system
Economic integrated capacitive voltage detecting system with relay
output