Accessing the connection compartment through the front
324 NXAIR / ≤ 40 kA 110-0134.9 / 14
23.6 Accessing the connection compartment through the switching-device compartment at panel
versions with ventilation system type II
WARNING
Reduced safety
The closed connection compartment is an important safety element of the
switchgear. The connection compartment is exclusively opened for performing
operational activities inside the connection compartment.
Close the high-voltage door:
If an activity inside the connection compartment is interrupted.
Immediately after an activity inside the connection compartment was
completed.
CAUTION
Sharp edges
The metal parts of the ventilation duct and the vertical partition may have sharp
edges.
Put on personal protective equipment.
CAUTION
High weight
The ventilation duct is heavy.
Remove the ventilation duct absolutely with 2 persons.
Put on personal protective equipment.
NOTICE
Damages to the ventilation duct
Loosening certain bolted joints could damage the ventilation duct.
When disassembling the ventilation duct, proceed exactly as described
hereafter. Do not loosen any bolted joints other than those described.

Table of Contents

Other manuals for Siemens NXAIR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens NXAIR and is the answer not in the manual?

Siemens NXAIR Specifications

General IconGeneral
BrandSiemens
ModelNXAIR
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals