Operating the circuit-breaker panel
40 NXAIR / 40 kA 110-0134.9 / 14
10.2 Position indicators visible on high-voltage door
Circuit-breaker:
CLOSED position or OPEN position
CLOSED
OPEN
Withdrawable circuit-breaker /
circuit-breaker truck:
Service position, intermediate position or
test position
Service position
Intermediate position
Test position
Spring state indicator:
CHARGED position or
NOT CHARGED position
CHARGED
NOT CHARGED
Feeder earthing switch:
CLOSED position or OPEN position
CLOSED
OPEN
10.3 Access to compartments
Regarding accessibility to the individual compartments, NXAIR switchgear fulfills the loss of service
continuity category LSC 2B according to IEC 62271-200.
The degree of protection between the individual compartments is IP2X in standard design.
The type of accessibility is provided as follows:
Compartment
Type of accessibility
Switching-device compartment
Interlock-controlled
Voltage transformer compartment
Tool-based
Busbar compartment
Tool-based
Connection
compartment
Access from the front side
Interlock-controlled and tool-based
Access from the rear side
Tool-based