Operating the circuit-breaker panel
40 NXAIR / ≤ 40 kA 110-0134.9 / 14
10.2 Position indicators visible on high-voltage door
Circuit-breaker:
CLOSED position or OPEN position
Withdrawable circuit-breaker /
circuit-breaker truck:
Service position, intermediate position or
test position
Spring state indicator:
CHARGED position or
NOT CHARGED position
Feeder earthing switch:
CLOSED position or OPEN position
10.3 Access to compartments
Regarding accessibility to the individual compartments, NXAIR switchgear fulfills the loss of service
continuity category LSC 2B according to IEC 62271-200.
The degree of protection between the individual compartments is IP2X in standard design.
The type of accessibility is provided as follows:
Switching-device compartment
Voltage transformer compartment
Access from the front side
Interlock-controlled and tool-based
Access from the rear side