Service information
110-0134.9 / 14 NXAIR / ≤ 40 kA 421
29.5 Lubricants to be used
Injury due to incorrect application
Incorrect application of the lubricants can cause injuries of the sense organs or the
hands.
Observe the safety instructions in the safety data sheets of the lubricant
suppliers.
Put on personal protective equipment.
Shutter guiding linkage (1)
WD-40 waterproof spray oil
ISOFLEX TOPAS L 32
(Order no.: 3AX1133-3E 1 kg)
Fixed contacts of feeder
earthing switch (3)
MOLYKOTE® LONGTERM 2
PLUS EXTREME PRESSURE
BEARING GREASE
(Order no.: 8BX1022 1 kg)
Main fixed contacts of bushings (4)
Fixed contacts of the switch-fuse
combination (5)
Fig. 746: Circuit-breaker, disconnecting, metering
and contactor panels
(panel width 600 mm)
Fig. 747: Contactor panel with panel width 435 mm
Fixed contacts of the feeder
earthing switch
Fixed contacts of the bushings
Fixed contacts of the feeder
earthing switch
Fixed contacts of the bushings