Panel heater
110-0134.9 / 14 NXAIR / ≤ 40 kA 415
28.3 Electronic temperature and humidity controller
Damage due to incorrect application
The temperature and humidity controllers require direct connection to the ambient
air.
Do not cover the ventilation slots of the temperature and humidity
controllers.
The electronic temperature and humidity controller can either be designed as a normally closed contact or as
a normally open contact:
If the ambient temperature falls below the adjusted value, the circuit for
heater operation is closed (LED lights up).
If the ambient temperature rises above the adjusted value, the circuit for
heater operation is open (LED does not light up).
If the relative humidity rises above the adjusted value, the circuit for heater
operation is closed (LED lights up).
If the relative humidity falls below the adjusted value, the circuit for heater
operation is open (LED does not light up).
Fig. 741: Electronic temperature and humidity controller
28.4 Applications for temperature controller
Maloperation
Observe the manufacturer's information.
Please do absolutely observe the enclosed operating instructions for the
temperature and humidity controllers.
Temperature for
application [°C]
Humidity for application,
not condensing [% r h]
Mechanical temperature controller
Electronic temperature and humidity controller
Selector for temperature control, with LED
Selector for humidity control, with LED