EasyManua.ls Logo

Siemens NXAIR - Page 406

Siemens NXAIR
436 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Panels with motor operating mechanism control
406 NXAIR / 40 kA 110-0134.9 / 14
Fig. 733: Circuit-breaker type 3AE1:
Inspection window for circuit-breaker
position and closing spring state
in control door
,
Fig. 734: Circuit-breaker type 3AE5:
Inspection window for circuit-breaker
position and closing spring state
in control door
NOTICE
Conflicting operation
The requirement of setting the panel to either local or remote control prevents
operating the panel locally and centrally at the same time.
For any local operations manual or electrical set the panel to local
control, for example by switching the local-remote switch to LOCAL
position.
NOTICE
Covered control elements
For safety reasons, some of the actuating openings involved in
charging / discharging the spring energy store are covered by the control door.
Open the control door to uncover the actuating openings on the high-
voltage door.
The procedures for charging / discharging the spring energy store manually in panels with motor operating
mechanism control are identical with the procedures in panels without motor operating mechanism control.
For charging / discharging the spring energy store manually, see chapters 10.14 and 10.15.

Table of Contents

Other manuals for Siemens NXAIR

Related product manuals