Operating the contactor panel with panel width 435 mm
140 NXAIR / ≤ 40 kA 110-0134.9 / 14
Permissible HV HRC fuse-links
The specified SIBA HV HRC fuse-links are motor protection back-up fuse-links according to IEC 60282-1.
The dimensions of the HV HRC fuse-links correspond to DIN 43625.
Maloperation
Contactor trucks are exclusively designed for operation with specific HV HRC
fuse-links. Using other types of fuse-links may cause damages on the panel.
Use only the fuse-link types listed in the following table.
Do not mount bridging links instead of HV HRC fuse-links.
Selection table for HV HRC fuse-links
Number of
fuse-links
permitted per
phase
Order details
(Inter-teknik)
+S68T.12KV.442.050.08-7.2
+S68T.12KV.442.063.08-7.2
+S68T.12KV.442.080.08-7.2
Supplier information : www.siba-fuses.com
Supplier information : www.inter-teknik.com
Number of
fuse-links
permitted per
phase
Order details
(Inter-teknik)
Supplier information : www.siba-fuses.com
Supplier information : www.inter-teknik.com