EasyManua.ls Logo

Siemens NXAIR - Page 158

Siemens NXAIR
436 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating the contactor panel with panel width 600 mm
158 NXAIR / 40 kA 110-0134.9 / 14
Procedure
NOTICE
Maloperation
All interlocks are only released when the contactor truck is in a stable end
position.
Rack the contactor truck absolutely until end position.
To release the actuating opening for the double-bit key, lift the operating slide and hold it.
To release access to the contactor truck, insert the double-bit key and turn
counter-clockwise as far as it will go (that is 90°).
Fig. 277: Lifting operating slide and
turning the double-bit key
counter-clockwise
Fig. 278: Operating shaft for
racking crank
Push the racking crank for moving the contactor truck onto the operating shaft, and turn
counter-clockwise as far as it will go.
Remove the racking crank for moving the contactor truck.