EasyManua.ls Logo

Siemens NXAIR - Page 16

Siemens NXAIR
436 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
16 NXAIR / 40 kA 110-0134.9 / 14
Height
Panel type
Dimension [mm]
I
k
31.5 kA
I
k
= 40 kA
Busbar version
2500 A
Busbar version
3150/4000 A
Busbar version
4000 A
With standard low-voltage compartment
2300
With high low-voltage compartment
2350
With pressure relief duct and arc absorber
2500
With natural ventilation
2300
With forced ventilation
2450
With additional compartment for busbar
components
2350
Depth
Panel type
Dimension [mm]
I
k
31.5 kA
I
k
= 40 kA
I
r
[A]
Panel width
[mm]
Busbar version
2500 A
Busbar version
3150/4000 A
Busbar version
4000 A
Circuit-breaker,
disconnecting,
bus sectionalizer,
busbar connection,
metering panel
2500
1350 or 1500
1500
1500
3150
1540 or 1650
1540 or 1650
4000
1540 or 1650
1540 or 1650
Rear duct version
≤ 4000
Panel version with rear duct is extended by 600 mm
Contactor panel
400
435
1400
1500
1500
400
600
1350
1500
1500
Switch-
disconnector panel
200
800
1350
1500

Table of Contents