EasyManua.ls Logo

Siemens NXAIR - Page 172

Siemens NXAIR
436 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating the contactor panel with panel width 600 mm
172 NXAIR / 40 kA 110-0134.9 / 14
Preconditions
High-voltage door closed
Contactor truck in test position
Padlock (optional) removed from operating slide
For electromagnetic interlock (optional):
Electromagnetic interlock deactivated
Operating lever available
Procedure
To release the actuating opening, lift the operating slide and hold it.
Fig. 307: Lifting the operating slide; actuating opening
While keeping the operating slide lifted, insert the operating lever slightly into the actuating
opening such that the pins in the operating lever are horizontal.
Insert the operating lever into the actuating opening as far as it will go.
Fig.308: Inserting the operating lever

Table of Contents

Other manuals for Siemens NXAIR

Related product manuals