Operating the contactor panel with panel width 600 mm
174 NXAIR / 40 kA 110-0134.9 / 14
Fig. 311: Removing the low-voltage connector
Hang the low-voltage connector into the support located underneath the low-voltage
compartment.
Fig. 312: Low-voltage connector stowed away
If no contactor truck is inserted in the panel and no further operation is executed: Close the
high-voltage door.
The removed low-voltage connector is lying in the support located underneath the low-
voltage compartment.
1
2