Operating the busbar connection panel type I
206 NXAIR / ≤ 40 kA 110-0134.9 / 14
Undetected damage
A tripped protection fuse-link can cause hidden damages on the other protection
fuse-links.
Always replace all protection fuse-links, even if only one protection fuse-
link has tripped.
Selection table for protection fuse-links:
Bussmann
(a business of Eaton)
7.2ABWNA / 3.15 A / 142 mm
Bussmann
(a business of Eaton)
12ABCNA / 3.15 A / 195 mm
Bussmann
(a business of Eaton)
Supplier information: www.eaton.com
Preconditions
• Withdrawable metering part / metering truck in test position
• Padlock (optional) removed from door handle
• High-voltage door open
• All voltage transformer MCBs switched to OPEN position
• Low-voltage connector stowed away
• Withdrawable metering part / metering truck taken out of the panel
• Set of proper protection fuse-links available
Replacing protection fuse-links for rated voltage ≤ 12 kV
Fig. 367: Withdrawable metering part,
taken out of the panel
Removable protection fuse-link
Fixed-mounted voltage
transformer