Operating the busbar current metering panel
110-0134.9 / 14 NXAIR / 40 kA 215
Preconditions
High-voltage door open
Hexagon socket head key size 6 available
Procedure
Close the high-voltage door using the handle (2).
Fig. 379: High-voltage door at the busbar current metering panel
Screw in 6 hexagon socket head bolts size 6 (1) by hand force. This corresponds to a
tightening torque of approx. 20 Nm.
The high-voltage door is closed.