EasyManua.ls Logo

Siemens NXAIR - Page 294

Siemens NXAIR
436 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating the shutters
294 NXAIR / 40 kA 110-0134.9 / 14
Opening the shutter to the connection
compartment (lower shutter)
Preconditions
Contactor truck in test position
Padlock (optional) removed from door handle
High-voltage door open
Contactor truck taken out of the panel
Fig. 541: Slip-on lever for opening the shutter;
vertical latching rod (2) pointing upwards
(1)
Roller
(2)
Latching rod
(3)
Handle of
latching rod
(4)
Main handle
On the left side in the switching-device compartment: Move the vertical interlocking lever (5)
upwards and padlock (6) the shutter mechanism.
Fig. 542: Padlocking the shutter mechanism on the left side in
the switching-device compartment
Take the slip-on lever by the main handle (4) with the vertical latching rod (2) pointing
upwards.
Turn to the right side in the switching-device compartment. Insert the rollers (1) of the slip-on
lever into the guide groove (7) of the shutter mechanism.
2
3
4
1
5
6

Table of Contents