Accessing the connection compartment through the front
308 NXAIR / 40 kA 110-0134.9 / 14
NOTICE
Damages inside the switching-device compartment
Damages inside the switching-device compartment due to incorrect or incomplete
installation of the partition.
To fasten the partition, always assemble all bolted joints of the partition all
around, and screw them in up to the end of the thread.
All panel versions except for contactor panels with panel width 435 mm and switch-disconnector panel:
In addition to these instructions, an instruction label on the vertical partition informs about safe fastening of
the partition:
Fig. 565: All panel versions except for contactor panels with panel width 435 mm and
switch-disconnector panel: Instruction label on the vertical partition
Preconditions
Feeder earthing switch in CLOSED position
High-voltage door open
Low-voltage connector stowed away
Panel versions with withdrawable circuit-breaker / circuit-breaker truck or
withdrawable disconnector / disconnector truck only:
Protection plate available
Connecting elements available: 4 nuts size M8
All panel versions except for contactor panels with panel width 435 mm and switch-disconnector
panel:
Partition available
Connecting elements available:
10 bolts M8x20 with contact washers and plain washers size 8
acc. to ISO 7093
5 bolts M8x20 with contact washers
Contactor panels with 435 mm width only:
Partition available
Connecting elements available:
7 bolts M8x20 with contact washers for left part of partition
4 bolts M8x16 with contact washers for right part of partition