Accessing the connection compartment through the rear
350 NXAIR / ≤ 40 kA 110-0134.9 / 14
All panel versions except for contactor panels with panel width 435 mm
and switch-disconnector panel:
Remove the connecting elements from the horizontal ledge (1):
• 8 bolts M8x25 with contact washers and plain washers size 8
acc. to ISO 7093
Remove the horizontal ledge, and store it together with the associated connecting elements.
Remove the connecting elements from one of the vertical ledges (2):
• 14 bolts M8x20 with contact washers
Remove the vertical ledge, and store it together with the associated connecting elements.
Proceed in the same way with the other vertical ledge.
Fig. 648: All panel versions except for contactor panels with panel width 435 mm
and switch-disconnector panel: 36 bolts on ledges
Remove the 2 sealing brackets (3), and store them.
Fig. 649: All panel versions except for contactor panels with panel width 435 mm
and switch-disconnector panel: Removing the sealing brackets